VARTA OPzV range 4 OPzV 200. . . 24 OPzV 3000
Application
VARTA OPzV Valve Regulated OPzV batteries are especially suitable for applications with discharge over a long period where maintenance-free operation is required. [. . . ] 1500 Ah) The safety provisions of the national and international standards must be observed.
Features Construction
Positive Electrode Negative Electrode Separation Tubular plate with VARTACalcium-Tin alloy Grid plate with calcium alloy Micro-porous separator, Combined with corrugated Separator Styrene acrylonitrile (SAN), impact resistant Dilute sulphuric acid Fixed as a gel Leakproof safety pole with brass insert, M10 Solid copper (30 x 3 mm), insulated, bolt-on type, for horizontal installation optional flexible cable connector (70 mm 2) 3/0 Safety pressure relief valve Float charge voltage: 2. 23 volts/cell at 20oC -10o. . . +45oC (Preferred value 20oC) · · · · · · 2V single cells Maintenance-free operation throughout its operational life due to valve regulated construction High level of operational safety due to pressure relief safety valve, safety pole, insulated connectors and fixed electrolyte Economic operation in capacitive discharge over several hours Space saving installation due to optimized set-up Low ventilation requirement, using the reduction factors
Casing Material Electrolyte Terminal Design Connectors
Vent Plugs Charging Temperature Range
VHB Industrial Batteries Ltd. · 72 Devon Road, Unit 22, Brampton, Ontario L6T 5B4 Tel: (905) 790-0730 · 1-888-VHB-BATT · Fax: (905) 790-0744 · E-mail: vhbbatt@vhbbatteries. com
Technical data
Type designation Capacity (Ah) C10 C8 C1
Final voltage
1. 80 1. 75 1. 688
Inner resistance
Theoretical short circuit current
without connectors, loaded [A] [mOhm/cell]
L 103 124 145
Cell dimensions (mm) (inch) * W H L W 206 206 206
Weight H
*
[kg]
[lb]
4 OPzV 5 OPzV 6 OPzV
200 206 250 257 300 309
1. 80
200 250 300
1. 75
124 156 187
1. 684
1. 22 0. 98 0. 81
1670 2090 2510
405 4. 06 8. 11 15. 94 405 4. 88 8. 11 15. 94 405 5. 71 8. 11 15. 94
19. 5 23. 5 27. 4
43. 0 51. 8 60. 4
Final voltage
5 OPzV 6 OPzV 7 OPzV
350 360 420 432 490 504
1. 80
350 420 490
1. 75
219 262 306
1. 625
0. 72 0. 60 0. 51
2830 3400 3960
124 145 166
206 206 206
520 4. 88 8. 11 20. 47 520 5. 71 8. 11 20. 47 520 6. 54 8. 11 20. 47
31. 5 37. 0 42. 4
69. 4 81. 6 93. 5
Final voltage
6 OPzV 600 618 8 OPzV 800 824 10 OPzV 1000 1030 12 OPzV 1200 1236
1. 80
594 791 992 1184
1. 75
382 510 637 764
1. 617
0. 53 0. 40 0. 32 0. 27
3800 5070 6340 7610
145 210 210 210
206 191 233 275
695 695 695 695
5. 71 8. 27 8. 27 8. 27
8. 11 7. 52 9. 17 10. 83
27. 36 27. 36 27. 36 27. 36
48. 8 67. 9 83. 2 98. 4
107. 6 149. 7 183. 4 216. 9
Final voltage
12 OPzV 16 OPzV 20 OPzV 24 OPzV
1500 2000 2500 3000
1545 2060 2575 3090
1488 1984 2480 2984
867 1156 1446 1735
0. 24 0. 18 0. 15 0. 12
8340 11120 13900 16680
210 212 212 212
275 397 487 576
845 822 822 822
8. 27 8. 35 8. 35 8. 35
10. 83 15. 63 19. 17 22. 68
33. 27 32. 36 32. 36 32. 36
123. 5 170. 6 210. 0 249. 3
272. 3 376. 1 463. 0 549. 6
*
The electrical values shown in the table relate to loadings from a fully charged condition and an ambient temperature of +25°C. Height includes connectors.
Project planning data
Final voltage = 1. 75V/cell Type 15' 4 OPzV 5 OPzV 6 OPzV 5 OPzV 6 OPzV 7 OPzV 6 OPzV 8 OPzV 10 OPzV 12 OPzV 12 OPzV 16 OPzV 20 OPzV 24 OPzV 200 250 300 350 420 490 600 800 1000 1200 1500 2000 2500 3000 168 209 250 287 343 397 405 540 676 811 918 1229 1531 1838 discharge current in A
30' 1h 2h 3h 5h 8h 10h
168 209 250 287 343 397 405 540 676 811 918 1229 1531 1838
118 148 177 206 246 287 316 421 526 632 735 982 1225 1470
74. 6 93. 3 111 129 155 182 213 284 355 426 506 676 844 1013
55. 4 69. 3 83. 1 97. 0 116 135 159 213 265 319 391 522 652 782
36. 9 46. 1 55. 4 64. 6 77. 6 90. 5 109 145 181 217 272 362 453 543
25. 0 31. 2 37. 5 43. 7 52. 5 61. 2 74. 3 98. 9 124 148 186 248 310 373
20. 6 25. 7 30. 9 36. 0 43. 2 50. 4 61. 8 82. 4 103 123 154 206 257 309
The current levels shown in the tables relate to loadings from a fully charged condition and an ambient temperature of +25°C. Connector losses are taken into account.
All dimensions and weights shown are subject to the usual manufacturing tolerances. The right is reserved to make alterations with a view to technically improved execution without prior notice. 04. 09. 01 0298 na
VARTA OPzV Solar
Longterm discharge capacities
Type
4 OPzV 200 5 OPzV 250 6 OPzV 300
C10 [Ah]
Uf = 1. 80 V/c 212 265 318
C24 [Ah]
Uf = 1. 85 V/c 240 299 359
C48 [Ah]
Uf = 1. 85 V/c 250 313 375
C120 [Ah]
Uf = 1. 85 V/c 254 318 382
C240 [Ah]
Uf = 1. 85 V/c 259 323 388
5 OPzV 350 6 OPzV 420 7 OPzV 490
383 459 536
433 519 606
452 542 632
460 551 643
467 560 654
6 OPzV 600 8 OPzV 800 10 OPzV 1000 12 OPzV 1200
696 928 1160 1392
786 1049 1311 1573
821 1095 1369 1643
835 1114 1392 1670
849 1132 1415 1698
12 OPzV 1500 16 OPzV 2000 20 OPzV 2500 24 OPzV 3000
1584 2112 2640 3168
1790 2387 2983 3580
1869 2492 3115 3738
1901 2534 3168 3802
1932 2577 3221 3865
Capacities are related to 20 °C. When cyclic charging and discharging only 80% of the capacity rating shall be used. [. . . ] Deep discharge does not lead to immediate capacity loss, but may reduce the operation life time.